MSA Ultima MOS-5 Manual do Utilizador Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 31
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
ULTIMA MOS 5 HART
9
10.6 Command #142: Reset Event Happened Flag
This command resets the Event Happened Flag.
Request Data Bytes
Byte Format Description
None N/A N/A
Response Data Bytes
Byte Format Description
None N/A N/A
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1 – 15 Undefined
16 Error Access Restricted
17 – 127 Undefined
10.7 Command #143: Read Event Logging Counters
This command reads five event logging counters.
Request Data Bytes
Byte Format Description
None N/A N/A
Response Data Bytes
Byte Format Description
0 – 1 Unsigned-16 Warning Event Counter
2 – 3 Unsigned-16 Alarm Event Counter
4 – 5 Unsigned-16 Fault Event Counter
6 – 7 Unsigned-16 Maintenance Event Counter
8 – 9 Unsigned-16 Calibrate Event Counter
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1-127 Undefined
Vista de página 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 30 31

Comentários a estes Manuais

Sem comentários