Features and Benets
Event logging stores fault, gas check, calibration, and alarm event history
4-20 mA output is the industry standard for remote alarm and fault indication
HART and ModBus communication provides complete status and control capability in
the control room
Detection ranges: 0-20 ppm, 0-50 ppm and 0-100 ppm enable a wide range of applications
Warning, Alarm & Fault Relays provide local alarm capability
Calibration, Calibration Check, and Set-up Modes simplify operation and maintenance
Remaining Sensor Life Indication reduces downtime by providing an estimate of
remaining sensor life
Wireless capability is compatible with ELPRO Technologies wireless devices
ULTIMA® MOS-5
Gas Detector
Description
The ULTIMA MOS-5 Intelligent Sensor is a micro -
processor-based transmitter designed for use with
MSAs Metal Oxide Semiconductor (MOS) sensor. This
unit features one person calibration and can virtually
self-calibrate through activation of a magnetic switch
and the application of gas. It is designed to detect
hydrogen sulde in parts per million (ppm) levels and
provide status indication and alarm outputs.
All of the ULTIMA MOS-5 Detector electronics are
contained within an explosion-proof housing so that
sensor information can be processed at the sensor
site. It provides a 4-20 mA signal which is propor -
tional to 0 to 100% of the detection range at the
sensor. In addition, the ULTIMA MOS-5 Detector
includes warning, alarm and fault relay contacts that
can be used to indicate an alarm or fault condition,
and dual redundant ModBus or HART communi -
cations. Congurations with relays, ModBus and
HART are available to meet many needs.
The ULTIMA MOS-5 Detector includes a three (3) digit
LED display. This local digital display continuously
indicates gas concentrations during normal opera -
tion and in the calibration check mode, calibration
prompts during calibration mode, display codes
during the setup mode and eight fault codes.
The ULTIMA MOS-5 Detector has four dierent
operating modes. The rst is the normal operating
mode in which alarms are active and the display and
4-20 mA readings are proportional to the gas
concen tration at the sensor. In the second mode, gas
check mode, the user can apply a gas and check the
sensor response while alarm outputs are inhibited.
The third mode, calibration mode, enables gas to be
applied to the sensor to calibrate the unit. Finally, a
set-up mode allows the user to review or change
setup options such as relay settings, sensor range,
and ModBus parameters.
Selecting Setup Mode on the ULTIMA MOS-5
Detector is accomplished by using the magnetic
switch, HART or ModBus command.
Options
• Sensor Range (0-20 ppm, 0-50 ppm, 0-100 ppm)
• Energized/de-energized relays
• Latching/non-latching relays
• Alarm setpoints for relays
• Baud rate, data format, and address for each ModBus channel
Intelligent Sensor for H
2
S Gas Detection
Vista de página 0
1 2 3 4

Resumo do Conteúdo

Página 1 - Gas Detector

Features and BenetsEvent logging stores fault, gas check, calibration, and alarm event history4-20 mA output is the industry standard for remote alar

Página 2

System SpecificationsSensor Type Continuous diusion,adsorption type Metal OxideSemiconductor (MOS)Sensor Life 3 to 5 years typicalRepeatability ±2 pp

Página 3 - Gas Transmitter

Features and BenetsRS-485 Dual ModBus Serial Interface in addition to 4-20 mA provides measurement, set-up and status of up to 247 nodes18.5-35 VDC o

Página 4 - 

System SpecificationsSensor Type Continuous diusion, Thin-m MOS,adsorption typeOver-range Indication Flashing readings in 99% - 120% ofselected meas